Scope T&M Pvt, Ltd.
Design electronic testing instruments that could work in the hostile electrical and electro-magnetic environment prevalent in charged sub-stations.
- 91-22-4344 4244
- 91-22-4344 4242
- 402, Aurus Chamber,
Annex A, S.S. Amrutwar, Marg,
Worli,, Mumbai 400 013
India
-
Product
Pre- Locator
CFL PL3
-
CFL PL3, new generation Cable Fault Pre-Locator from SCOPE is the ultimate solution for locating underground cable faults in minimum time. It uses advanced technology for fault distance measurement which helps even an unskilled operator to locate the fault with accuracy.
-
Product
Contact Resistance Meter
CRM 200B
-
CRM 200B directly measures micro-ohm values at 100 Amps DC under live switchyard conditions.CRM 200B is specially designed to reliably measure contact resistance of circuit breakers, isolators, busbar joints, welded joints etc., under the hostile electrostatic noise found in live EHV switchyards upto 765 kV.
-
Product
Circuit Breaker Testing Equipment (SCOT Series)
SCOT MXP+
-
SCOT MXP+ measures, displays and prints CLOSE, OPEN and CLOSE-OPEN time of 2 Main + 2 PIR contacts per pole, 3 poles simultaneously, ensuring measurement of 6 Main + 6 PIR contacts simultaneously. Ideally suitable for CBs having PIR contacts & multiple breaks per pole
-
Product
Circuit Breaker Testing Equipment
HISAC Swift
-
HISAC Swift - Circuit Breaker Operational Analyser is meant for checking the performance of the MV Circuit Breakers. The Analyser contains various intelligent measuring modules designed for measuring parameters such as contact timings of Main/PIR & Auxiliary contacts, Close/Trip Coil Current characteristics and Static Contact Resistance of R, Y & B poles simultaneously. The results can be directly viewed on the TFT touch screen display in graphical as well as numerical form. It is possible to print the graph on a built-in thermal printer or download record to PC for further analysis on CPLOT software. This all in one instrument is best suited for gang operated CBs.
-
Product
Pre- Locator
CFL PL2+
-
The new generation CFL PL2+ Cable Fault Prelocator from SCOPE is the ultimate solution for locating underground cable faults in minimum time. It uses advanced technology for fault distance measurement which helps even an unskilled operator to locate the fault accurately up to 50 km.
-
Product
Thermal Imaging Camera
TI160 - P5
-
TI 160-P5 is a special thermal imaging camera for human body temperature measurement only. Its has Accurate temperature measurement, real-time imaging, ability to quickly lock the hot-spot. It is been widely used in airports, docks,railway stations, schools, shopping malls and other public places to check human body temperature abnormalities. Palmetto design, compact and lightweight, integrated visible light function. Reliable performance and accurate temperature measurement can effectively improve the efficiency of detection.
-
Product
Pre- Locator
CFL PL4
-
CFL PL4 Power Cable Fault Locator is a portable, easy to use cable fault pre-location instrument. It uses the Time Domain Reflection (TDR), Secondary Impulse Method / Multiple Impulse method (MIM) and Impulse Current Method (ICM) on low, medium and high voltage cables. Its measuring ranges enable pre-location on cable lengths from 500 m to 64km.
-
Product
Winding Resistance Meter
TRM 25
-
SCOPE introduces 25 A state of the art precision winding resistance meter, specially designed for field testing as well as factory testing of large transformers up to 500 MVA. Winding resistance value of transformer and rotating machine are directly displayed on 5.7” TFT display. TRM 25 is designed to work in live EHV switchyard conditions, ensuring operator’s safety and repeatability of results. Maintenance time saving is ensured by one time connection to transformer with simultaneous resistance measurement of three / six windings, measurement of resistances of all taps with automated tap change and demagnetization facility. The meter is protected against the back-EMF offered by large inductive windings.
-
Product
Earth Resistance Meter
EM 4058
-
earth tester is a digital, microprocessor controlled instrument that allows to measure the earth resistance and ground resistivity (using Wenner´s method), as well as to detect parasitic voltages present in the ground. This instrument is suitable to measure earth systems in power substations, industries, distribution networks, etc., according to IEC 61557-5.
-
Product
Circuit Breaker Testing Equipment (SCOT Series)
SCOT M3K
-
SCOT M3K measures and displays CLOSE, OPEN and CLOSE-OPEN time of main contacts of 3 poles connected end to end, simultaneously.
-
Product
CT Polarity Tester
DIR CT
-
SCOPE proudly introduces Dir CT, a CT Polarity Tester specially designed to verify correctness of polarity of current transformers cores in live EHV switchyards. Polarity test is one of the most common yet crucial tests required to be done on current transformers by commissioning as well as maintenance engineers. Even though it is commonly conducted check, there was no all in one simple tool available for this measurement. DIR CT fills this void to perfection, it is expected to significantly reduce the time taken for polarity checks on numerous CT in sub-station, especially during commissioning of new sub-stations
-
Product
Insulation Resistance Measurement
MD 5060x
-
The Megabras MD-5060x is a smart, microprocessor-controlled, 5kV insulation tester and analyzer. Besides the conventional measurement of insulation resistances up to 5 TW, its advanced features allow to automatically measure both the Polarization Index and Dielectric Absorption Index, thus significantly simplifying testing of transformers.
-
Product
Surge Arrestor Testing Equipment
SA 30i
-
SA 30i, the Leakage Current Analyser from SCOPE is a State of the Art, On-line test system for Residual Life Assessment of Metal Oxide Surge Arresters. The instrument measures and directly displays the values of Total Leakage Current and Third Harmonic Resistive Leakage Current. It provides system harmonic compensation as per IEC 60099-5-B2. It provides Corrected Resistive Leakage Current after applying correction factors for change in system voltage & temperature.